APC ACCD75208 Manual de Serviço

Consulte online ou descarregue Manual de Serviço para Componentes de arrefecimento para computador APC ACCD75208. APC Condenser 1 EC Fan Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Technical Data

InRow® RPChilled Water/Direct Expansion — 50/60 HzTechnical DataAIR-COOLEDACRP100ACRP101ACRP102CHILLED WATERACRP500ACRP501ACRP502

Página 2

InRow RP Technical Data Manual6Optional FeaturesCable Water DetectorA leak detection cable is placed on the floor or subfloor around all possible leak

Página 3 - Contents

7InRow RP Technical Data ManualMicroprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each system. The contro

Página 4

InRow RP Technical Data Manual8AlarmsThe microprocessor controller shall activate a visible and audible alarm in the following occurrences:• Cool Fai

Página 5 - Overview

9InRow RP Technical Data ManualInRow RP ModelsHinged rear doorsCasters (all swiveling)Side panel lockDoor handle and lockRemovable side panelDis

Página 6 - Environments

InRow RP Technical Data Manual10Chilled Water Interior Components (front of unit)Electric heater (for reheat)Electrical panelFanSupply temperature

Página 7 - Hot Aisle Containment System

11InRow RP Technical Data ManualChilled Water Interior Components (back of unit)Chilled water coilRear doorsChilled water control actuatorAir filt

Página 8 - Standard Features

InRow RP Technical Data Manual12Air-cooled Interior Components (front of unit)Electric heater (for reheat)Main circuit breakerCondensate drain pan

Página 9

13InRow RP Technical Data ManualAir-cooled Interior Components (back of unit)Evaporator coilShutoff valves (top piping only)Condensate drain panAi

Página 10 - Optional Features

InRow RP Technical Data Manual14Chilled Water and Air-cooled User Interface ConnectionsRack inlet temperature sensors 1, 2, 3A-Link INA-Link OUTNe

Página 11 - Microprocessor Controller

15InRow RP Technical Data ManualChilled Water Electrical PanelNote: ACRP501 shown. Transformers User interface connectors Main controller board Re

Página 12 - Air-cooled Only Alarms

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Página 13 - InRow RP Models

InRow RP Technical Data Manual16Air-cooled Electrical PanelNote: ACRP 101 shown. Transformers User interface connectors Main controller board Rela

Página 14

17InRow RP Technical Data ManualPerformance SpecificationsChilled Water Performance Specifications 5.5°C (42°F) EWTTemperature dry bulb (DB), wet bulb

Página 15

InRow RP Technical Data Manual18Chilled Water Performance Specifications 7.2°C (45°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (

Página 16

19InRow RP Technical Data ManualChilled Water Performance Specifications 8.9°C (48°F) EWT (Temperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Página 17

InRow RP Technical Data Manual20Chilled Water Performance Specifications 10°C (50°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C (°

Página 18

21InRow RP Technical Data ManualChilled Water Performance Specifications 12.8°C (55°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Página 19 - Note: ACRP501 shown

InRow RP Technical Data Manual22Chilled Water Performance Specifications 15.5°C (60°F) EWTTemperature dry bulb (DB), wet bulb (WB)°C (°F)CW Delta T°C

Página 20 - Air-cooled Electrical Panel

23InRow RP Technical Data ManualChilled Water Data - GeneralMODEL ACRP 500 SeriesMODULATING VALVESSize -3 Way Ball Valve - NPT mm (in) 25.4 (1)AIR SYS

Página 21 - Performance Specifications

InRow RP Technical Data Manual24Glycol Correction FactorsAltitude Correction Factors for InRow ProductsAir-cooled Performance SpecificationsPerformanc

Página 22

25InRow RP Technical Data ManualAir-cooled Data - GeneralNote: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low i

Página 23

ContentsInRow RP Technical Data ManualiOverview ... 1Capacity . . . . . . . .

Página 24

InRow RP Technical Data Manual26Sound Performance DataElectrical DataChilled Water Tested Sound DataFan Speed% Airflow m3/s (SCFM)Sound Power dB at F

Página 25

27InRow RP Technical Data ManualDimensional DataInRow RP Assembled ModuleDimensions are shown in mm (in).na2465a

Página 26

InRow RP Technical Data Manual28SX to VX Height AdapterSX to 48U SX Height AdapterDimensions are shown in mm (in).na2445ana2446a

Página 27 - Chilled Water Data - General

29InRow RP Technical Data ManualPiping and Mechanical ConnectionsChilled Water Piping DiagramFlex hose or copper Circuit setter (field-installed)Coppe

Página 28 - Glycol Correction Factors

InRow RP Technical Data Manual30Top Chilled Water Piping Access (top view)Note: Top or bottom entry can be chosen individually for each type of connec

Página 29 - Air-cooled Data - General

31InRow RP Technical Data ManualBottom Chilled Water Piping Access (bottom view, looking up)Dimensions are shown in mm (in).Water supply to chillerW

Página 30 - Electrical Data

InRow RP Technical Data Manual32Air-cooled Piping DiagramNote: Shutoff valves shown nearest to the condensers are not supplied by APC.Note: Route pipi

Página 31 - Dimensional Data

33InRow RP Technical Data ManualAir-cooled Piping Access (top)Dimensions are shown in mm (in). Refrigerant discharge line Refrigerant liquid line P

Página 32 - SX to 48U SX Height Adapter

InRow RP Technical Data Manual34Air-cooled Piping Access (bottom view, looking up)Dimensions are shown in mm (in).Pressure relief valve access—27.80

Página 33 - Chilled Water Piping Diagram

35InRow RP Technical Data ManualAir-Cooled CondensersMechanical DataSKUAmbient TempSound Pressure (dbA)*Sound Pressure (dbA) **Air Quantity Fan Unit C

Página 34

InRow RP Technical Data ManualiiInRow RP Models ... 9Chilled Water Interior Components (front

Página 35

InRow RP Technical Data Manual36ACCD75201 and ACCD75204ACCD75202 and ACCD75205ACCD75203 and ACCD75206Dimensions are shown in mm (in).Note: All condens

Página 36 - Air-cooled Piping Diagram

37InRow RP Technical Data ManualACCD75207ACCD75208 and ACCD75209Dimensions are shown in mm (in). All condensers shown on this page have 16 m

Página 37

InRow RP Technical Data Manual38Guide SpecificationsPART 1 — GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for

Página 38

39InRow RP Technical Data ManualB. VARIABLE SPEED FAN ASSEMBLY1. Variable Speed Fans: The unit is equipped with variable speed, electronically commuta

Página 39 - Air-Cooled Condensers

InRow RP Technical Data Manual40k. Fan faultl. Fan run hours exceededm. Water detection faultn. Condensate pump faulto. Condensate run hours exceededp

Página 40 - ACCD75203 and ACCD75206

41InRow RP Technical Data Manualba. Air flow decreased while compressor offbb. Suction pressure sensor failurebc. Discharge pressure sensor failurebd.

Página 41 - Air-cooled Condenser Features

InRow RP Technical Data Manual42J. CONDENSATE PUMPFactory installed and wired condensate pump shall pump at 31.99 l/h (8.45 GPH) at 3.5 m (11.5 ft) of

Página 42 - Guide Specifications

43InRow RP Technical Data ManualP. SELECTABLE TOP OR BOTTOM PIPING (AIR-COOLED ONLY)1. Pipe connections: The unit is equipped with field connection fr

Página 43 - 460-480V 60Hz 22

InRow RP Technical Data Manual44Guidelines for InstallationThe InRow RP provides reliable, accurate temperature control of computer rooms, laboratorie

Página 45

1InRow RP Technical Data ManualOverviewThe modular, row-based computer room cooling system offers efficient, predictable, and economical cooling for a

Página 46

9/2009990-2469E-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Página 47

InRow RP Technical Data Manual2Scalable Solution for Critical EnvironmentsInRow AdvantagesThe row-based solution improves energy efficiency and coolin

Página 48 - Guidelines for Installation

3InRow RP Technical Data ManualHot Aisle Containment System Modular ceiling tiles and doors can be used to enclose the hot aisle. This increases the d

Página 49

InRow RP Technical Data Manual4Standard FeaturesInsulated CabinetThe frame is constructed of 1.5 mm (16 gauge) formed steel for maximum strength. Cabi

Página 50 - 9/2009990-2469E-001

5InRow RP Technical Data ManualDual Position Float Condensate ManagementThe pump is factory wired and piped internally to the condensate drain pan and