InRoom CW/DX – Operating Instructions 65
The reheat is optional for your cooling unit. It is installed complete and integrated in the function and me-
thod of operation of the cooling unit. It is used to heat up the air. The following versions of the heater are
available:
- Electrical reheat
Electrical reheat
The reheat is connected in accordance with the electric di-
a gram. It is con trolled and monitored by the controller. The
values for switching on and off are adjusted in the "operate
module functions/heating" menu on the controller. Refer to
the operating instructions for the InRoom controller.
Operation
The reheat is controlled and monitored by the controller. No further measures
are required for operation.
Maintenance
Clean the reheat annually from contaminations and check it for damage.
9.2 Reheat
Description
Commissioning
The reheats are controlled and monitored by the controller of your cooling unit as well as high temperature
limit switches. The high temperature limit s
witch is set at 125°F (fi xed). No further measures are required
for commissioning.
Installation
The reheats are installed and connected in the cooling unit.
Malfunction causes
Alarm: Reheat defect
All reheat alarms are received by the controller and can be requested according to the equipment.
InRoom advanced terminal: indication on the display
Electrical Hazard:
Repairs to the electrical components are only to be carried out by APC authorized person-
nel.