19InRow RD Technical Data Manual
Performance Specifications
Net Cooling Capacity (Air and Glycol Cooled)
Return Air Temperature SKU Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)
22.2°C DB, 15.5°C WB (72°F DB, 60°F WB)
ACRD100 8.22 (28,000) 8.04 (27,400)
ACRD101 8.01 (27,200) 7.71 (26,400)
ACRD200 8.22 (28,000) 8.04 (27,400)
ACRD201 8.01 (27,200) 7.71 (26,400)
ACRD500 series 22.8 (78,000) 19.0 (65,000)
23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB)
ACRD100 8.52 (29,000) 8.52 (29,000)
ACRD101 8.16 (27,900) 8.16 (27,900)
ACRD200 8.52 (29,000) 8.52 (29,000)
ACRD201 8.16 (27,900) 8.16 (27,900)
ACRD500 series 25.2 (86,000) 21.7 (74,000)
26.7°C DB, 19.4°C WB (80°F DB, 67.0°F WB)
ACRD100 10.02 (34,000) 9.12 (31,000)
ACRD101 9.72 (33,200) 8.85 (30,200)
ACRD200 10.02 (34,000) 9.12 (31,000)
ACRD201 9.72 (33,200) 8.85 (30,200)
ACRD500 series
N/A N/A
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
ACRD100 9.36 (32,000) 9.36 (32,000)
ACRD101 8.97 (30,700) 8.97 (30,700)
ACRD200 10.02 (34,000) 9.12 (31,000)
ACRD201 9.72 (33,200) 8.85 (30,200)
ACRD500 series 26.9 (92,000) 26.9 (92,000)
29.4°C DB, 18.1°C WB (85°F DB, 64.6°F WB)
ACRD100 9.90 (33,800) 9.90 (33,800)
ACRD101 9.69 (33,100) 9.69 (33,100)
ACRD200 9.90 (33,800) 9.90 (33,800)
ACRD201 9.69 (33,100) 9.69 (33,100)
ACRD500 series 29.0 (99,000) 29.0 (99,000)
32.2°C DB, 19.0°C WB (90°F DB, 66.2°F WB)
1
ACRD100 10.44 (35,600) 10.44 (35,600)
ACRD101 10.29 (35,200) 10.29 (35,200)
ACRD200 10.44 (35,600) 10.44 (35,600)
ACRD201 10.29 (35,200) 10.29 (35,200)
ACRD500 series 30.5 (104,000) 30.5 (104,000)
35.0°C DB, 19.9°C WB (95°F DB, 67.8°F WB)
2
ACRD100 10.62 (36,200) 10.62 (36,200)
ACRD101 10.5 (35,900) 10.5 (35,900)
ACRD200 10.62 (36,200) 10.62 (36,200)
ACRD201 10.5 (35,900) 10.5 (35,900)
ACRD500 series 33.7 (115,000) 33.7 (115,000)
37.8°C DB, 20.7°C WB (100°F DB, 69.3°F WB)
3
ACRD100 10.62 (36,200) 10.62 (36,200)
ACRD101 10.5 (35,900) 10.5 (35,900)
ACRD200 10.62 (36,200) 10.62 (36,200)
ACRD201 10.5 (35,900) 10.5 (35,900)
ACRD500 series 36.9 (126,000) 36.9 (126,000)
40.6°C DB, 21.6°C WB) (105°F DB, 70.8°F WB
4
ACRD100 10.56 (36,000) 10.56 (36,000)
ACRD101 10.5 (35,900) 10.5 (35,900)
ACRD200 10.56 (36,000) 10.56 (36,000)
ACRD201 10.5 (35,900) 10.5 (35,900)
ACRD500 series 36.6 (125,000) 36.6 (125,000)
43.3°C DB, 22.2°C WB) (110°F DB, 72.0°F WB
5
ACRD100 10.6 (36,000) 10.6 (36,000)
ACRD101 10.5 (35,900) 10.5 (35,900)
ACRD200 10.6 (36,000) 10.6 (36,000)
ACRD201 10.5 (35,900) 10.5 (35,900)
ACRD500 series N/A N/A
Airflow for the ACRD100 and 200 series is 1081 l/s (2290 SCFM) at full evaporating fan speed.
Airflow for the ACRD500 series is 2171 l/s (4600 SCFM) at full evaporating fan speed.
1
Airflow is reduced to 887 l/s (1880 SCFM) at this condition to maintain adequate evaporating temperature.
2
Airflow is reduced to 717 l/s (1520 SCFM) at this condition to maintain adequate evaporating temperature.
3
Airflow is reduced to 599 l/s (1270 SCFM) at this condition to maintain adequate evaporating temperature.
4
Airflow is reduced to 510 l/s (1080 SCFM) at this condition to maintain adequate evaporating temperature.
5
Airflow is reduced to 448 l/s (950 SCFM) at this condition to maintain adequate evaporating temperature.
Note: Minimum recommended loads: ACRD100 series and ACRD200 series - 2kW (6,831 BTU); ACRD500 series - 10kW (34,152 BTU)
Note: For ACRD100 and ACRD500 series the outdoor air temperature is 35° C (95° F)
Note: For ACRD200 series, a 40% at 0.64 l/s (10gpm), the entering glycol mixture temperature is 40.6° C (105° F)
Note: For ACRD500 series, reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).