55User Guide InfraStruxure 150kVA Power Distribution Unit
icAlarm
Access: Administrator, Device
Description: Enable/disable alarm of the targeted input contact.
Parameters: <alarm>
alarm = enable|disable
Example:
apc> icStatus
1. New Contact 1,Critical,Critical,Open,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4
apc> icAlarm disable //disabling clears the alarm
1. New Contact 1,Normal,Critical,Closed,Door Switch
apc> icStatus
1. New Contact 1,Normal,Critical,Closed,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4
icSeverity
Access: Administrator, Device
Description: Enable/disable alarm of the targeted input contact.
Parameters: <severity>
alarm = critical|warning
Example:
apc> icStatus
1. New Contact 1,Critical,Critical,Open,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4
apc> icSeverity warning
1. New Contact 1,Normal,Warning,Closed,Door Switch
apc> icStatus
1. New Contact 1,Normal,Warning,Closed,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4