NetShelter AV 42 U Enclosure Unpacking, Installation, and Customization Manual14
Grounding the Enclosure
Each enclosure should be grounded directly to the building ground using one of the designated
grounding locations (two M6 threaded inserts) at the top or bottom of the enclosure.
Use a Common Bonding Network Jumper kit (for example, Listed [KDER] Panduit
RGCBNJ660PY or equivalent).
Use paint-piercing washers between ground terminal and enclosure frame or remove paint on
frame under ground terminals per NEC NFPA 70 Article 250.12.
Torque screws to 6.9 N-m (60 in-lb).
Do not ground one enclosure to another enclosure in a cascading style.