5.0 Operation
5.1 Front-panel indicators
5.1.1 Very High input voltage indicator
The Very High indicator lights when the power conditioner is regulating
input voltage which is approaching the upper limit of the conditioner’s
rated range.
5.1.2 High input voltage indicator
The High indicator lights when the power conditioner is regulating
input voltage which is above normal.
5.1.3 Normal input voltage indicator
The Normal indicator lights when the input voltage is normal.
5.1.4 Low input voltage indicator
The Low indicator lights when the power conditioner is regulating
input voltage which is below normal.
5.1.5 Very Low input voltage indicator
The Very Low indicator lights when the power conditioner is regulating
input voltage which is approaching the lower limit of the conditioner’s
rated range.
5.1.6 Surge Protection Integrity indicator
The Surge Protection OK indicator lights when the power conditioner
is on and operating normally. The indicator is off when the power
conditioner has disconnected itself from the input service because of a
sustained high-energy surge, or the unit is overloaded. If the indicator is
off, check the rear-panel circuit breaker, and reset it if necessary.
5.3 Audible alarm
The power conditioner will sound an audible alarm when it detects ex-
treme input voltages that it cannot correct. Such high or low voltages will
cause output voltages outside the conditioner’s rated regulation band.
For 120 Vac models, the audible alarm sounds when the input voltage is
outside the range 85–150 Vac. For 230 Vac models, the audible alarm sounds
when the input voltage is outside 162–299 Vac.