General characteristics of MGE TM Galaxy TM 7000 UPSs >
34020846EN/AD - Page 61
2. Appendices
2.4 General characteristics of MGE
TM
Galaxy
TM
7000 UPSs
UPS power in kVA 250 300 400 500
Normal AC input
Number of conductors 3 phases
Reference voltage at Pn 380 V to 415 V
Reference frequency 45 Hz to 66 Hz
THDI Typically 3% at Pn
Power factor > 0.99
Bypass AC input
Number of conductors 3 phases + neutral
Reference voltage at Pn 380 V to 415 V
Reference frequency 45 Hz to 66 Hz
Load output
Number of conductors 3 phases + neutral
Set phase-to-phase voltages 380 V / 400 V / 415 V
Set phase-to-neutral voltages 220 V / 230 V / 240 V
Voltage variation ± 1%
Adjustable frequencies and tolerance
(on battery power)
50 Hz or 60 Hz ± 0.1 Hz
Voltage variation for 0 to 100% load
step change
± 1%
Permissible overloads 150% for 30 seconds, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N for
nonlinear load
< 2% Ph-to-Ph
Battery
Standard battery technology Sealed lead-acid battery (gas-recombination)
(Valve Regulated Lead Acid type)
UPS
PN/2 PN PN/2 PN PN/2 PN PN/2 PN
Active power (kW) 112 225 135 270 180 360 225 450
Efficiency 94.1 94 94 94 94.1 94 94 94.3
Heat losses in kW
Heat losses in calories/s
7
1673
14.3
3418
8.6
2055
17.2
4111
11.2
2676
22.9
5473
14.3
3418
27.2
6500
Storage temperature range -25°C to +45°C
Operating temperature range at Pn 0°C to 35°C
Relative humidity 45% to 75%
Maximum operating altitude without
derating
< 1000 m
Noise level (dBa) 75
Product standards IEC 62040
Safety standards IEC 62040-1-2
Protection standards IEC 62040-3
EMC standards IEC 62040-2