Apc UPS control system Manual do Utilizador Página 180

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 233
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 179
MAXLINEV is the maximum line voltage since the last STATUS as
returned by the UPS.
MINLINEV is the minimum line voltage since the last STATUS as re-
turned by the UPS.
OUTPUTV is the voltage the UPS is supplying to your equipment.
SENSE is the sensitivity level of the UPS to line voltage fluctuations.
DWAKE is the amount of time the UPS will wait after a power off con-
dition when the power is restored.
DSHUTD is the grace delay that the UPS gives after receiving a power
down command from apcupsd before it powers off your equipment.
DLOWBATT is the remaining runtime below which the UPS sends the
low battery signal. At this point apcupsd will force an immediate
emergency shutdown.
LOTRANS is the line voltage below which the UPS will switch to bat-
teries.
HITRANS is the line voltage above which the UPS will switch to batter-
ies.
RETPCT is the percentage charge that the batteries must have after a
power off condition before the UPS will restore power to your equip-
ment.
STATFLAG is a status flag indicating the UPS status. See STATUS.
ITEMP is the internal UPS temperature as supplied by the UPS.
ALARMDEL is the delay period for the UPS alarm.
BATTV is the battery voltage as supplied by the UPS.
LINEFREQ is the line frequency in Hertz as given by the UPS.
LASTXFER is the reason for the last transfer to batteries.
NUMXFERS the number of transfers to batteries since apcupsd startup.
XONBATT time and date of last transfer to batteries, or N/A.
TONBATT time in seconds currently on batteries, or 0.
CUMONBATT total (cumulative) time on batteries in seconds since
apcupsd startup.
179
Vista de página 179
1 2 ... 175 176 177 178 179 180 181 182 183 184 185 ... 232 233

Comentários a estes Manuais

Sem comentários