APC ACRD200 Especificações Página 36

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 44
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 35
InRow Fluid Cooled RD Installation28
Building Management System (BMS)
The Modbus interface allows each InRow RD to communicate with the BMS. Use a three-wire cable to
connect each InRow RD in turn. Wire a 150-Ohm, 1/4-W terminator resistor (included) into the Modbus
master and the final InRow RD between Modbus D0 and Modbus D1.
Each InRow RD has a three-wire Modbus terminal on the user interface. Use a connector with screw
terminals to attach wiring. See “User interface connections” on page 24 for a diagram of the user
interface.
For information on setup of Modbus parameters, see the InRow RD Operation manual.
Termination resistor (provided)
Modbus cable (RS-485)
na2678a
InRow RD #1 InRow RD #2 Final InRow RD
Modbus master
Vista de página 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 42 43 44

Comentários a estes Manuais

Sem comentários