3 Site Preparation & Installation Guide Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI
Warning: Stop using the unit immediately if any of the following conditions arise.
•Conduit or receptacles have been damaged
•Objects have fallen into the unit
•Liquid has spilled into the unit
•The unit has been exposed to rain
•The unit has been dropped or damaged in any way
•The unit does not operate properly
Contact APC at www.apc.com, to arrange service for the unit.
Specifications
UTS Specifications UTS6/UTS6H UTS6BI UTS10BI
Electrical
Input - Utility
Input line Circuit: 12 AWG
Neutral: 10 AWG
Circuit: 12 AWG
Neutral: 10 AWG
Circuit: 12 AWG
Two Neutral: 10 AWG
Voltage range 84 Vac to 142 Vac 84 Vac to 142 Vac 84 Vac to 142 Vac
Nominal voltage 120 Vac/240 Vac
single phase
120 Vac/240 Vac
single phase
120 Vac/240 Vac
single phase
Rated voltage 120 Vac 120 Vac & 240 Vac 120 Vac & 240 Vac
Allowable frequency 47 Hz to 63 Hz 47 Hz to 63 Hz 47 Hz to 63 Hz
Rated current 20 A per circuit 20 A per circuit 20 A per circuit
Input - Backup1 (Generator)
Nominal voltage UTS6 model:
120 Vac/240 Vac
split phase
UTS6H model:
120 Vac single phase
120 Vac/240 Vac
split phase
120 Vac/240 Vac
split phase
Rated voltage 120 Vac 120 Vac & 240 Vac 120 Vac & 240 Vac
Frequency 47 Hz to 63 Hz 47 Hz to 63 Hz 47 Hz to 63 Hz
Rated Current UTS6 model:
20 A
UTS6H model:
30 A
20 A
30 A
50 A hardwired
Maximum voltage 84 Vrms to 142 Vrms 84 Vrms to 142 Vrms 84 Vrms to 142 Vrms
Input - Backup2 (UPS)
Input line IEC 320 male IEC 320 male IEC 320 male
Nominal voltage 120 Vac single phase 120 Vac single phase 120 Vac single phase
Rated voltage 120 Vac 120 Vac 120 Vac
Frequency 47 Hz to 63 Hz 47 Hz to 63 Hz 47 Hz to 63 Hz
Rated Current 15 A 15 A 15 A
Maximum voltage range 84 Vrms to 142 Vrms 84 Vrms to 142 Vrms 84 Vrms to 142 Vrms