Installation Manual
21
How to Install Multiple Management Cards
Overview
When installing more than one management card, such as the Network Management
Card (NMC), the Out-of-Band Management Card, etc., you must install the cards in
the order described in this document. This is because they share a serial link with the
UPS. Installing the cards in any other order might result in operational failure.
Before you start
The following table identifies the priority of the cards you will be installing.
Management cards that have more control over the UPS have higher priority.
Level 6: Exerts total control
Level 5: Exerts wide, but not total, control
Level 4: Exerts limited control
Level 3: Passes commands to the UPS
Level 2: Exerts no control
Level 1: Exerts no control and must be installed closest to the UPS
Two models of expansion chassis
If you need management card slots in addition to those in your UPS, use one or
more expansion chassis available.
Management Card Priority
Network Management Card
1
(AP9630, AP9631) Level 6
Out-of-Band Management Card (AP9608) Level 5
Relay I/O Module (AP9613, AP9610) Level 4
Interface Expander Card (AP9607) Level 3
Building Management Integration Card
2
(AP9622) Level 2
Environmental Monitoring Card Level 1
1. Attach no more than two Network Management Cards to a UPS.
2. Attach only one Building Management Integration Card to a
UPS.
Chassis Compatible UPS Devices
Expansion Chassis (AP9600), one slot
UPS devices that are not
installed in a rack or enclosure.