USER’S GUIDE
NetBotz Rack Monitor 200
105
XMODEM
1. Download the latest firmware release for your NetBotz Rack Monitor 200
(NBRK0200) from www.apc.com/tools/download.
2. Create a directory to which you will extract the files.
3. Double-click the file you downloaded from the APC Web site and follow the
prompts to extract the files to the folder created in the previous step. You will
download to the Main Module two files extracted: the APC Operating System
(AOS) file and the NetBotz application file. When a window opens and prompts
you for the IP Address, close the window.
4. Select a serial port at the local computer and disable any service using the port.
5. Connect the provided RS-232 configuration cable to the selected port and to
the serial port at the Main Module.
6. Run a terminal program such as HyperTerminal, and configure the selected
port for 9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.
7. Press
ENTER to display the User Name prompt.
8. Enter the Administrator user name and password (apc by default for both).
9. From the Control Console menu, select System, then Tools, then File
Transfer, then XMODEM; and type Yes at the prompt to continue.
10. Select a baud rate, change the terminal program’s baud rate to match your
selection, and press
ENTER. A higher baud rate causes faster upgrades.
11. From the terminal program’s menu, select and transfer the binary AOS file
using XMODEM-CRC. After the XMODEM transfer is complete, set the baud
rate to 9600. The Main Module automatically restarts.
12. Repeat step 6 through step 11 to install the application module. In step 11, use
the application file name, not the AOS file name.
For a successful firmware upgrade, you must first transfer the AOS file and then
transfer the application file.