Standard Features
APC NetworkAIR™ FM-DX 7
Steam Generating Humidifier
The humidifier utilizes a pure steam
generator specifically designed for
precision environmental control.
The pure steam eliminates contami-
nating mineral deposits, potentially
harmful bacteria, white dust and
excessive humidity. The humidifier
requires little scheduled mainte-
nance. Automatic flushing
combined with a communication
link to the controller signals when
the canister is to be changed.
Humidifier is proportionally con-
trolled to meet the humidification
demands of the conditioned space.
The communication link to the
main controller provides diagnostic
capability for the humidifier.
High Return Air Temperature
Capability
All NetworkAIR FM units are
equipped to handle the high return
air temperatures associated with
today’s high density applications.
Refrigerant Charge Isolation
For compressor protection, the Net-
workAIR FM utilizes charge
isolation and crank case heaters
during compressor off-cycles. This
eliminates the threat of liquid
refrigerant migration that could lead
to compressor slugging and lubrica-
tion issues.
Refrigeration System Monitoring
The system reports real time moni-
toring of both suction and discharge
pressures to the controller. Pres-
sures shall be logged and displayed
at the proper menu selection on the
controls.
High Lift, Dual Float Condensate
Pump
The factory installed and wired con-
densate pump is capable of
pumping 60 gal/hr (0.06 L/s) at 60
ft. (18.3 m) head.
30% ASHRAE 52.1 Filters
The filtration of conditioned air is
extremely vital to maintaining the
clean, particle-free environment
required by electrical equipment.
The system uses 30% efficient (100
microns) (ASHRAE 52.1-92), 4”
(102 mm) deep filters, with full
depth filter pleats. Deeper filters
produce a lower pressure drop,
requiring less energy during normal
operation. Filters are replaceable
through the front of the upflow unit,
and through the top of the down-
flow unit.
SCR Controlled Electric Reheat
Electric reheat elements are low
watt density, wired for 3-phase and
loaded equally on all three phases,
SCR controlled, and electrically
and thermally protected by both
automatic and manual reset thermal
cut outs. Reheat coils are stainless
steel, fin tubular construction.