USER’S GUIDE
network management card
87
Put UPS To
Sleep
This option puts the UPS into sleep mode by turning off its output power
for a defined period of time, as follows:
• The UPS turns off output power after waiting the time configured as
its Shutdown Delay.
• When input power returns, the UPS turns on output power after two
configured periods of time: its Sleep Time and Return Delay.
• For a synchronized control group action, the Management Card of
the UPS initiating the action waits up to the number of seconds
configured as its Power Synchronized Delay for enabled group
members to regain input power before it starts the Return Delay. If
all group members have already regained input power, the Power
Synchronized Delay is omitted. If all group members regain input
power during the delay, the remainder of the delay is cancelled.
Put UPS To
Sleep
Gracefully
1
(control
console)
This action puts the UPS into sleep mode (turns off power for a defined
period of time), as follows:
• The UPS turns off output power after waiting the delay times
configured as its Maximum Shutdown Time plus 2 minutes (to
allows time for PowerChute network shutdown to safely shut down its
server) and its Shutdown Delay.
• When input power returns, the UPS turns on output power after two
configured periods of time: its Sleep Time and Return Delay.
• For a synchronized control group action, the Management Card of
the UPS initiating the action waits up to the number of seconds
configured as its Power Synchronized Delay for enabled group
members to regain input power before it starts the Return Delay. If
all group members have already regained input power, the Power
Synchronized Delay is omitted. If all group members regain input
power during the delay, the remainder of the delay is cancelled
Put UPS In
Bypass
Take UPS Off
Bypass
Controls the use of bypass mode, which allows maintenance to be
performed at a Matrix-UPS, a Symmetra UPS, and some Smart-UPS
models without turning off power at the UPS.
Action Definition
1 When you select Yes for the Web interface’s Signal servers option, initiating a Turn UPS
Off, Reboot UPS, or Put UPS To Sleep action is equivalent to selecting Turn UPS Off
Gracefully, Reboot UPS Gracefully, or Put UPS To Sleep Gracefully in the control
console.