Appendix B Uninterruptible Power Supply
B.5. Power On
When powering on the subsystem, the UPS must be powered on before the subsystem. To
see how to power on the UPS, please refer to the documentation that came with your
UPS. Note that the power on sequence described in Chapter 4 will be altered. The power
on sequence when a UPS is connected is shown below:
Step 1. Power on the network connection devices (including FC switches).
Bypass this step if you are using a SCSI host subsystem.
Step 2. Power on any expansion/cascaded enclosures connected to the
subsystem.
Step 3. Power on the UPS.
Step 4. Power on the subsystem.
Step 5. Power on the application servers.
Step 6. The subsystem firmware should detect the UPS. To see how to do this
please, refer to the Generic Operation Manual that came with the
subsystem.
NOTE:
A UPS can be connected to the subsystem after the subsystem has been powered on,
but you will have to trigger the firmware to allow the subsystem to detect the UPS.
B.6. UPS Status Monitoring
If a UPS is correctly connected to the subsystem, the status of the UPS will be constantly
monitored by the controller through the COM2 (audio jack) serial port. The status of the
UPS will determine the controller’s write policy, and messages that appear on the LCD
panel and other monitoring devices will keep you informed of the UPS status.
Power On B-3