Using the RAID GUI
2-47
Record Event Log
Click Configure and specify the Lowest severity of events option for the events you want to record on NVRAM. The
events with severity levels higher than the specified one will be recorded. The default severity level is info, which means
events of all severity levels will be recorded.
Send a Test Mail
Click Configure and specify the Severity of testing event option to send a test mail. A testing event record will be
generated according to the selected severity level. This helps users to test the event logging and notifications setup.
2.9.4 UPS
The UPS Control option enables or disables the UPS function when the controller is started. When this option is set to
On, the controller will automatically detect if the UPS is connected or not.
To configure the UPS settings, do the following:
1. Select Event management > UPS from the main menu, you can view the UPS information, status, and battery status
here.
2. Click Configure and specify the following options.
3. Click Apply to confirm the current settings.
2.9.5 Miscellaneous
Note
Before sending out the test mail, you need to turn on the event notification and specify the event
receivers. (Refer to 2.9.1 Setting up the SMTP on page 2-44.)
Change Date (YYYY/MM/
DD)
This option resets the latest battery replacement date.
Delay Shutdown
(seconds)
90 / 180 / 270 / 360 / 450 / 540 / 630
When a power failure occurs and the UPS battery charge is below the normal
range, the UPS will power down after the specified delay time.
Delay Boot (seconds) 0 / 60 / 120 / 180 / 240 / 300 / 360 / 420
The UPS automatically powers on after the specified delay time. This avoids
branch circuit overload when AC power returns.
Low Battery Threshold
(seconds)
120 / 300 / 480 / 660 / 840 / 1020 / 1200 / 1380
This option notifies the user that the UPS battery is low, with the specified
remaining seconds.
Change Restart
Percentage
0 / 15 / 30 / 45 / 60 / 75 / 90
After the AC power returns, the UPS does not power on until the battery charge
reaches the specified capacity.
Note
1. The values from each drop-down menu may be different according to the UPS connected.
2. Currently the controller only support and communicate with Smart-UPS function APC
(American Power Conversion Corp.) UPS. Please check detail http://www.apc.com/.
Beeper Control: On (default) / Off / Mute
This option controls the controller’s beeper.
On: The beeper sounds during exceptional conditions or when background tasks make progress. By default, the
beeper is on.
Off: The beeper is quiet all the time.
Mute: This temporarily mutes the beeper, but it beeps again if exceptional conditions still exist.
Auto Write-Through Cache