InRow Air Cooled RD Installation24
Leak sensor (optional)
Install one leak sensor (AP9325). To extend the
leak sensor length, add up to three additional leak
sensors (AP9326).
1. Connect the leak sensor to the equipment
using the leak detector port as shown.
2. Position the leak sensor inside or outside the
equipment.
3. Route the leak sensor to the outside through
either the bottom plate or the door.
4. Secure the leak sensor wire to surfaces using
cable ties and cable tie holders (provided with
the leak detector).
na1584a na2760a
AP9325
AP9325
na2676a
Leak detector port
na2675a
Note: Install leak sensors on a
clean surface, and do not allow
them to touch metal that is in an
air stream.