InRow Air Cooled RD Installation32
Building Management System (BMS)
The Modbus interface allows each InRow RD to communicate with the BMS. Use a three-wire cable to
connect each InRow RD in turn. Wire a 150 Ohm, 1/4-W terminator resistor (included) into the
MODBUS master and the final InRow RD between Modbus D0 and Modbus D1.
Each InRow RD has a three-wire Modbus terminal on the user interface. Use a connector with screw
terminals to allow wiring to be attached. See “User interface connections” on page 28 for specific layout
of the user interface.
For information on setup of Modbus parameters, see the InRow RD Operation manual.
Termination resistor (provided)
Modbus cable (RS-485)
na2678a
InRow RD # 1 InRow RD # 2 Final InRow RD
Modbus master