InRow RD Operation and Maintenance6
User Interface Inspection Checklist
The user interface inspection verifies that the sensors and internal communication links are installed
properly. Check that the outdoor heat exchanger is connected to the cooling unit and to the other cooling
units in the room if you are using cooling group controls.
Ensure that:
An A-Link bus is connected to each cooling unit and a terminator is plugged into all unused A-Link
connectors.
The input contacts and output relays are connected correctly.
The building management system is connected correctly and a terminator is wired into the final InRow
RD between Modbus D0 and Modbus D1.
The temperature and humidity sensors located on the front of the cooling unit are connected correctly.
The rack temperature sensors are installed correctly.
The network port is connected correctly and an IP address has been assigned to the equipment.
The optional rope water detection device is installed properly.