InRow RD Operation and Maintenance30
Compressor Drive: Voltage. The compressor voltage.
Compressor Drive: Current. The compressor current draw.
Compressor Drive: DC Link. The compressor internal direct current (DC) link voltage.
Compressor Drive: Heat Sink. The compressor heat sink temperature.
Compressor Drive: Ctrl Card (Control Card). The compressor control card temperature.
Compressor Drive: Warn Stat. The compressor warning word used for diagnostics.
Compressor Drive: Alrm Stat. The compressor alarm word used for diagnostics.
Cooling group status
Path: Main > View Group Status
View information about the cooling group.
Cool Output. The combined output of the cooling group.
Cool Demand. The cooling output required to meet the current heat load of the conditioned space.
Cool Setpt. The temperature you set to maintain the room environment.
Max Rack. The highest rack temperature reported by any cooling unit in the cooling group.
Min Rack. The lowest rack temperature reported by any cooling unit in the cooling group.
Air Flow. The combined airflow output of the cooling units in the cooling group.
About the cooling unit
Path: Main > About InRow RD
View identifying information that is helpful when obtaining service:
Model: Model number
S/N: Serial number
F/W: Display interface firmware revision
H/W: Hardware revision
Made: Date of manufacture
RP APP: Application version
AOS Ver: APC OS version