APC NetworkAIR CM Series: Standard Features 7
Standard Features
Thermostat
controller
The unit control provides two separate heat and cool temperature setpoints
with a minimum 2° F spacing between them. The controller shall activate
heating or cooling functions automatically in regards to setpoint versus
measured conditions. The control setpoint range shall be 60° F to 85°F. Units
requiring humidity control have separate humidity and dehumidity setpoints
with a minimum 4% RH spacing between them. The controller activates
humidifying or dehumidifying cycles as a function of setpoint versus
measured return air conditions.The humidity setpoint range shall be 20% RH
or 80% RH. As an option, the control shall also allow daily or 5 day/2 day
program scheduling at a maximum of 2 programs per day.
Overall cabinet The frame is constructed of heavy gauge steel for maximum strength. Hanger
mounting brackets shall be part of the chassis and shock mounts are provided
for vibration isolation. The unit offers service access to all components
through removable access panels lined with 1/2" thick insulation for noise
reduction.
Blower assembly The CM series includes a centrifugal blower assembly that has been
engineered for quite, reliable operation. Lower blower speeds reduce noise.
Permanently lubricated bearings, a single-belt variable pitch drive, and an
adjustable motor base insure dependable operation on the 4 and 5 ton models.
The 1 to 3 ton models are direct drive selections. In addition, the air return
patterns evenly distribute air across the cooling coil.
Electrical panel The electrical panel contains the contactors, starters, overload protection
devices, and input power circuit breakers. Each wire (except jumpers) is
numbered every 3" (80 mm), or color coded to facilitate circuit tracing when
installing and servicing the unit. Each AC power circuit is individually
branch circuit fused on all three phases. All compressor and motor devices
are thermally and short circuit protected. The electrical panel is easily
accessible from the front of the unit, and its modular construction allows
access to major components within the unit cabinet. All electrical
components are UL-listed and-recognized and all wiring conforms to NFPA
70 (NEC) and UL 1995 requirements.
Humidifier The humidifier utilizes a pure steam generator specifically designed for hi-
tech area environmental control. The pure steam eliminates contaminating
mineral deposits, potentially deadly bacteria, white dust and excessive
humidity. The humidifier requires little or no scheduled maintenance.
Automatic flushing combined with an indicator that signals when the canister
is to be changed, ensure maintenance free operation.