10 APC NetworkAIR CM Series: Optional Features
Setpoints. The microprocessor is provided with independent setpoints for:
Automatic setpoint crossover protection will prevent the setting of the heat
setpoint above the cool setpoint and the humidify setpoint above the
dehumidify setpoint. Setpoint adjustment can be restricted to only operators
with knowledge of the security codes set within the security menu structure.
Configuration. Flexibility is offered through the use of the configuration
menu. Operating requirements are satisfied by changing the configuration
settings. New configurations are stored in EEPROM and protected from
unauthorized tampering by the four-digit security password, selected in the
security menu.
Configuration options include:
Common alarm contact. A common alarm relay is installed on every
microprocessor. In the event of an alarm condition, the relay will change
state. The user can select which alarms change the state of the relay. This
feature allows for remote enunciation of alarm status.
Run times. The major components within the unit (motor, humidifier, and
compressor) have independent run timers that monitor and store accumulated
run hours on the components. The run timers are provided with operator
adjustable run time alarms.
Security. Multiple security levels prevent unauthorized adjustment of
important system parameters. The user may select a four-digit password for
setpoint and configuration changes. Should the password be forgotten, APC
can provide temporary access.
Monitoring. With the addition of a network communications card the
microprocessor may interface with the locally installed APC remote
monitoring and control system. Gateways are available for interfacing with
building management systems. Please check with APC for compatibility with
your building management system.
Cool inhibit. Prevents the unit from over-cooling during the
dehumidification cycle. If the space temperature falls below a user adjustable
setpoint, cooling will become inhibited until the space temperature returns to
setpoint.
Cool override. A manual toggle switch will allow one compressor operation
in the event of a microprocessor failure. The cool override can be field wired
to a snap acting thermostat for cooling control.
• Heating • Humidification
• Cooling • Dehumidification
• Fahrenheit or celsius display • Alarm input polarity
• Compressor minimum on time • Alarm enable
• Compressor minimum off time • Temperature deadbands
• Power loss restart time delay • Humidity deadbands
• Redundant unit grouping • Small room delay