APC INROOM ACPSC3000 Instruções de Operação Página 15

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 106
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 14
15InRoom Controller - Operating Instructions
Pin
14
13
12
11
10
9
8
7
6
5
4
3
2
1
CPU
X12
X4
RS485 Driver for the BMS bus
Jumper X2: bus termination for RS 485 I/O-bus
Pos. A: set, Pos. B: not set
Jumper X3: bus termination for RS 485 BMS-bus
Pos. A: set, Pos. B: not set
RS485 Driver for the IO bus
RS232 - BMS port (SUB-D 9)
RS232 - service port (SUB-D 9)
Fuse T1A
Jumper X6: Pos. A: Board in download mode
Contrast adjustment for display
Real-
time
clock
Technical Data:
Dimensions: 270 x 110 x 40 mm
Voltage supply: 24(
+15%) VAC
Power consumption: 14 VA
Fuse: 2 A time-lag
Operating temp.: 5°C...40°C
Storage temp.: -30°C...60°C
2.5 InRoom Controller Board
2.5.1 Board design
Pin Designation Function
14 Port 2-L
RS485 BMS-bus
13 Port 2-H
12 Port 1-L
RS485 I/O-bus
11 Port 1-H
10-3 Free terminal none
2 GND
Power supply
1 +24VAC
Position
A B
Vista de página 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 105 106

Comentários a estes Manuais

Sem comentários