InRoom Controller - Operating Instructions70
➊
➋
➌
➍
➎
➏
R3
5 min.
S
fix
dS
S
var
➊
T/°C
➋
R4
Service
The corresponding commands:
Display Gen. settings
Control/Parameters (Part 2)
The controller has the option of starting a
stand-by unit after an adjustable positive
temperature difference to the air tempera-
ture setpoint is achieved. This difference
can be adjusted by the parameter "Load
-
start"
➏ . The adjustment 0.0K disables
this function.
The sequencing function is not influenced
by starting a standby-unit.
The outside temperature
➊ for the com-
mutation from summer to winter operation
is decisive for the drycooler and com-
pressor control. With this hysteresis
➋
the winter operation changes to summer
operation.
The winter operation is also switched over
to summer operation if an outside temp.
sensor breakdown is detected. An alarm
"Outside temperature sensor defect" is
not displayed.
The winter start delay
➌ inhibits the low
pressure monitoring on alarm conditions
for an adjustable time in 0-255 seconds,
which is relevant for the compressor
operation.
You can determine an integral factor
➍
for the air temperature control to avoid a
control discrepancy which is characteristic
for P-controllers. In this case a variable
setpoint S
var, which is recalculated every
5 minutes is decisive for the control. This
variable setpoint is calculated by adding
the setpoint alteration dS to the previous
setpoint.
The values for the integral factor can be
varied between 0 an 80%. A low value
should be used to start with in order to
prevent the control system from oscillating.
10% are recommended and can stepwise
be increased to find out the limit of safe
control.
For details of the cooling priority ➎ see
next page.
actual value
time
Svar
n+1
= Svar
n
+ dS with
dS = (Sfix - actual value ) x integral factor
sfix represents the fixed setpoint which
is adjusted in the menu Control/Tem-
perature.
Summer
Winter
sumwin start 16.0
sumwin hys 2
winterdelay 180
integral 10
coolingprio 1
load 2.5