87InRoom Controller - Operating Instructions
Range Louver 1 Louver 2 Louver 3
Pre-start
0 - 180 90 s 90 s 90 s
Output D 0 - 31 7 10 18
Component configure
d 0 - 1 0 0 0
Range Sensor 1 Sensor 2 Sensor 3 Sensor 4
Purpose 1 - 16 1 2 3 4
Input A 1 - 21 1 2 3 4
Type
1 - 5 1 1 1 1
Component configure
d 0 - 1 1 1 1 1
Min. measure value -50 - 100 0°C (-50 - 100) 0%r.h (0 - 100) 0°C (-50 - 100) 0%r.h (0 - 100)
Max. measure v
alue -50 - 100 50°C (-50 - 100) 100%r.h (0 - 100) 50°C (-50 - 100) 100%r.h (0 - 100)
Min. output value 0 - 20 4 mA (0 - 20) 4 mA (0 - 20) 4 mA (0 - 20) 4 mA (0 - 20)
Max. output value
0 - 20 20 mA (0 - 20) 20 mA (0 - 20) 20 mA (0 - 20) 20 mA (0 - 20)
Max.
difference 0 - 100 10% 10% 10% 10%
Limit - alarm priority
0 - 31 0 0 0 0
Limit - common alarm
0 - 1 1 1 1 1
Limit - alarm delay 0 - 100 5 s 5 s 5 s 5 s
Failure - alarm priority
0 - 31 0 0 0 0
Failure -common alarm
0 - 1 1 1 1 1
Failure - alarm delay
0 - 100 5 s 5 s 5 s 5 s
Offset
-10.0 - 10.0 0°C 0% r.h. 0°C 0% r.h.
Range Sensor 5 Sensor 6 Sensor 7 Sensor 8
Purpose 1 - 16 5 7 11 12
Input A 1 - 21 5 6 7 8
Type
1 - 5 1 2 1 1
Component configure
d 0 - 1 1 1 1 1
Min. measure value -50 - 100 -50°C (-50 - 100) -20°C (-50 - 100) 0 bar (0 - 35) 0 bar (0 - 35)
Max. measure v
alue -50 - 100 50°C (-50 - 100) 40°C (-50 - 100) 30 bar (0 - 35) 30 bar (0 - 35)
Min. output value 0 - 20 0 mA (0 - 20) 0 V (0 - 20) 4 mA (0 - 20) 4 mA (0 - 20)
Max. output value
0 - 20 20 mA (0 - 20) 10 V (0 - 20) 20 mA (0 - 20) 20 mA (0 - 20)
Max.
difference 0 - 100 10% 10% 10% 10%
Limit - alarm priority
0 - 31 0 0 0 0
Limit - common alarm
0 - 1 1 1 1 1
Limit - alarm delay 0 - 100 5 s 5 s 5 s 5 s
Failure - alarm priority
0 - 31 0 0 0 0
Failure -common alarm
0 - 1 1 1 1 1
Failure - alarm delay
0 - 100 5 s 5 s 5 s 5 s
Offset
-10.0 - 10.0 0°C 0°C 0 bar 0 bar
Louver
Sensors