75InRoom Controller - Operating Instructions
Stand
-by
Stand
-by
Stand
-by
Stand
-by
Stand
-by
Stand
-by
Stand
-by
Zone 02
Zone 02
Zone 02
Failure dependent change-over
Definition of valid alarms for one zone
For each zone any number out of 26 alarms in total can be defined as valid alarms.
If such an alarm occurs the corresponding unit is switched off and notified as de-
fective.
All 26 alarms are defined as valid alarms by default. The alarm "unit not available"
can not be deleted from the alarm list. This alarm is always part of the valid alarms
and appears due to a bus failure or when the unit has locally been switched off.
After the failure of a unit a standby unit is switched on. With the switching on of the
last available standby unit the time dependent sequencing is interrupted.
When the previously adjusted number of defective units in one zone is reached the
emergency operation is enabled for all zones.
Emergency operation means that the emergency temperature of the triggering zone
is accepted as the new temperature set value for all the zones.
The number of defective units is independent of the number of standby units which
have been started. For example, even if the failing unit capacity of one zone is
completely equalled by the start of standby units, the defective units are counted
as lacking.
To start an emergency operation just when the 100% unit capacity (without standby
units) is not achieved anymore, the adjusted number of defective units should be
higher than the number of a zone's standby units.
deletes valid alarm 2
adds alarm 2 as valid alarm
displays list of all available alarms
Unit 02 Unit 04 Unit 05
Cycle 1
Unit 06 Unit 09 Unit 10
Unit 02 Unit 04 Unit 05
Cycle 1
Unit 06 Unit 09 Unit 10
Unit 02 Unit 04 Unit 05
Cycle 2
Unit 06 Unit 09 Unit 10
Failure dependent change-over
Due to
a failure of
unit 04 unit 05 is
switched on.
For safety reasons, valid alarms can only be configured by commands.
The corresponding commands:
Valid alarms:
--.Not available 01.Local stop
02.Compressor lowpressure 03.Compressor Failure
04.E-heating Failure 05.Humidifier Failure
06.Humidifier 5uS 07.Humidifier 20uS
08.Fan error 09.Filter clocked
10.External alarm 11.Pump Failure
12.Drycooler Failure 13.Water detector
14.Roomtemp too high 15.Roomhumidity too high
16.Supplytemp too high 17.Supplyhumidity too high
18.Roomtemp too low 19.Roomhumidity too low
20.Supplytemp too low 21.Supplyhumiduty too low
22.Watertemp too high 23.Watertemp too low
24.Fire/smoke detector 25.Sensor Failure
26.Sensor broken
zone 1 alarm 2 0
zone 1 alarm 2 1
zone 1 alarm h