49InRoom Controller - Operating Instructions
D6
t/sec
%
100
90
nMax
80
70
65
55
t/sec
100%
nmax
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Air
Fan (Part 2)
With the parameter "START 100%" you
adjust a time which must elapse before the
control begins. This way an airflow alarm is
avoided which could occur due to the fan
inertia. During this time the fan is operated
with 100% speed.
Using the "PRERUN" parameter you
adjust the delay for the inhibited start of
all components, except the glycol pump, in
relation to the control start with alarm moni
-
toring. This way the Pre-run parameter has
the effect of a cooling unit start delay. Using
different pre-runtimes for different units
saves power and ensures that the power
supply of the building will not overcharge.
The fan over-run time ("HUNTING TIME")
, which you can adjust, serves to reject
hot or cold air in the cooling unit and avoids
an accumulation of heat at the reheat or of
cold at the evaporator.
If during a time which you adjust with "RE-
DUCE TIME" no action (cooling, heating,
humidification, dehumidification) has been
taken, the fan speed is reduced by the per
-
centage which you adjust with "REDUCE
SPEED" .
The "FILTER OFFSET" is entered as a
positive difference to the maximum speed.
If a filter alarm is released, the maximum
speed will be increased by the filter offset
in order to overcome the higher resistance
of a clogged filter.
(except the reducing time which is entered
in minutes)
control
start
Fan start phase
compon.
start*
fan
start
*start of all other control-relevant components
except the glycol pump, which can be started
earlier.
unit stop
Fan stop phase
fan stop
over-run due
to fan inertia
filter offset
offset a*
reduced speed
dehumidif. speed **
UPS speed **
*this item refers to the previous page.
** these parameters are explained on
the overnext page.
Speed levels
fan 1 100 5
fan 1 pre 15
fan 1 after 20
fan 1 redtime 30
fan 1 redspeed 20
fan 1 filteroffset 15