InRoom Controller - Operating Instructions74
Stand
-by
Stand
-by
Stand
-by
Stand
-by
Zone 01
Zone 01
Q5
Display
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Gen. settings
Sequencing
The zone concept is based on the idea to
obtain a homogeneous room climate within a
determined space by distributed generation
of conditioned air. Within a zone only one
room temperature exists, which is calculated
as the average value of all connected room
temperature sensors of the units in opera-
tion; this also applies to the room humidity,
1. Sequencing
Within a zone you can have a unit sequencing with change-over dependent on
time and failure.
The following parameters must be specified for this:
. Unit assignment
A zone is defined by the assignment of units. A maximum of 32 zones can be
defined with the adjustments from 1 to 32. Zone 0 means that the unit is assigned
to no zone. The assignment is made individually for each unit.
. Standby units
When a sequencing takes place the zone must contain at least one standby unit.
This setting must be made for each unit/IOC by means of the ON/OFF-button on
the InRoom Controller.
. Number of defective units (errorunits) (zone parameter)
This entry is optional. If the number, adjusted here, is reached, the emergency
operation will be put into force.
. Emergency temperature (zone parameter)
This temperature is the new sepoint when emergency operation is enabled.
Time dependent changeover
The cycletime
determines the lapse of time after which a changeover will peri-
odically take place. This means that the standby status is changed over the units
one by one. With the setting 0 (hrs) no sequencing is made.
Setting the cycletime causes the sequencing start after the sequencing menu has
been left.
To let the standby units (set under item
) participate in the sequencing, they have
to be locally switched on by means of the ON/OFF-button on the InRoom Controller.
For this the corresponing unit must be selected in the bus overview window.
Enabling the test sequencing
with the fixed cycletime of 5 minutes helps you to
check the sequencing function.
supply temperature, and supply humidity. The set values can be individually adjusted
for each unit, but they should only vary slightly.
There are two zone specific functions:
1. Sequencing 2. CW standby management
assigns unit 7 to zone 1
deletes unit 7 from zone 1
puts unit 3 into standby
switches unit 3 on
en- (1) or disables (0) test sequencing
Time dependent change-over
(normal sequencing)
e. g. with 2 standby units:
1. cycle unit 07, 11 standby
2.
cycle unit 08, 14 standby
3.
cycle unit 11, 01 standby
etc.
Unit 01 Unit 03 Unit 07
Cycle 1
Unit 08 Unit 11 Unit 14
Unit 01 Unit 03 Unit 07
Unit 08 Unit 11 Unit 14
Cycle 2
zone 1 + 7
zone 1 - 7
zone 1 unit 3 0
zone 1 unit 3 1
zone 1 emernum 3
zone 1 emertemp 15.7
zone 1 seqtime 10
zone 1 test 1