InRoom Controller - Operating Instructions60
➊
➋
➌
➍
K6
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Cooling
Drycooler
In the first line you add the drycooler to the
configuration by entering "1". With "0" you
disable the drycooler. ➊
With the parameter "D-OUT" you determi-
ne a digital output for the drycooler on/off
signal.
➋
The digital input for the drycooler alarm can
be assigned by the "D-IN" parameter. ➌
The drycooler runtime can be set in the
last line. ➍
Note:
For the dry cooler control, the configuration
of an outside temperature sensor and a
water temperature sensor is required.
drycool 1 conf 1
drycool 1 dout 10
drycool 1 alarm 5
drycool 1 runtime 150