InRoom Controller - Operating Instructions66
➊
➋
➌
➍
➎
➏
O5
P5
➐
➑
➒
➓
O7
Service
The corresponding commands:
Display Equipment
Aux. Ports/Aux. Ports
You can adjust digital in- and outputs for
non-component-related alarms or messages
in this window.
In detail you can adjust the digital output for
the common alarm
➊ and for the wintermode
➋. The wintermode signal can be forwarded
to a BMS system.
You can also adjust the digital inputs for the
remote contact
➌, the fire alarm ➍ and the
water detector ➎, which creates the water
alarm and for the UPS operation
➏.
In the following window you can assign the
digital inputs for the phase failure alarm ➐
and for the external cooling priority ➑. (See
page 71).
You can also determine the analogous
outputs for the external use of the actual
temperature
➒ and the actual humidity ➓.
Aux. Ports/Unit alarms
In this window you can assign digital inputs
to unit alarms. The fire alarm
➍, the water
detector ➎, which creates the water alarm,
and the phase failure alarm
➐.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
calarm dout 7
winter dout 17
remote din 11
fire din 12
water din 8
ups din 13
phase din 19
cwoff din 16
curtemp aout 3
curhumi aout 5